HMP230 SERIES
M210225en-B User's Guide
71
9. TECHNICAL DATA
9.1. Relative humidity
Measuring range 0...100 %RH
Accuracy (including nonlinearity and repeatability)
maximum achievable accuracy when calibrated against high quality,
certified humidity standards:
±1 %RH (0...90 %RH)
±2 %RH (90...100 %RH)
when calibrated against salt solutions (ASTM E104-85):
±2 %RH (0...90 %RH)
±3 %RH (90...100 %RH)
Response time (90 %) at +20 °C in 15 s
still air (with sintered filter)
Sensors
HUMICAP
®
K: humidity sensor with blue dots
on the sensor
HUMICAP
®
KC: combined RH and T sensor
(part no.18258HM)
9.2. Temperature
Measuring range
HMP231 -40...+60 °C
HMP233 -40...+80 / +120 °C
HMP234/235/237/238 -40...+180 °C
Typical accuracy of electronics at
+20 °C (+68 °F) ±0.1 °C
Typical temperature dependence of
electronics 0.005 °C/°C
Sensor Pt 100 RTD 1/3 Class B IEC 751
9.3. Calculated variables
Typical ranges - HMP231
dewpoint temperature -40...+60 °C
mixing ratio 0...160 g/kg dry air
absolute humidity 0...160 g/m
3
wet bulb temperature 0...+60 °C
enthalpy -40…+460 kJ/kg