Chapter 4 ________________________________________________________________ Operation
VAISALA _______________________________________________________________________ 33
Show Analog Output Status
The AOUT command shows the following information:
- Analog out mode is the output mode for the channel, for example
0 ... 10 V.
- Error level is the level that the analog output is set to in case of
transmitter error.
- Status indicates the current status of the channel. The statuses are
- ON: Normal measurement operation.
- OFF: No quantity selected for the channel using the ASEL
command. See section Set/Show Analog Output Quantity and
Scaling on page 42.
- ERROR: Transmitter error, channel set to error level.
- TEST: Analog channel being tested using the ATEST
command. See section Test Analog Outputs on page 44.
AOUT<cr>
Example:
>aout
*** ANALOG OUTPUT 1 ***
Ch1 Analog out mode : 0_10V
Ch1 Error level : 10.8
Ch1 Quantity : RH
Ch1 Status : ON
RH lo : 0
RH hi : 100
RH : 36.64 %
Ch1 Voltage : 3.66 V
*** ANALOG OUTPUT 2 ***
Ch2 Analog out mode : 0_10V
Ch2 Error level : 10.8
Ch2 Quantity : T
Ch2 Status : ON
T lo : -60
T hi : 100
T : 23.85 'C
Ch2 Voltage : 5.24 V
>
Page view 34