112
GMW115 Carbon Dioxide Transmitter for
Demand-controlled Ventilation
The Vaisala CARBOCAP
®
Carbon Dioxide Transmitter GMW115 is a wall-mounted
CO
2
transmitter for demand-controlled ventilation.
Most of us spend 90 % of our time
indoors. Consequently, good indoor
air quality is important to our
wellbeing. All human beings produce
carbon dioxide gas by respiration,
thus the carbon dioxide level can
be used as an indicator for indoor
human presence. A high CO
2
level is a
sign of poor ventilation and often an
indication of other unpleasant odors
in the air. In many buildings the
ventilation need varies throughout
the day. Demand controlled
ventilation is an economical way to
ensure good air quality.
The Vaisala CARBOCAP
®
CO
2
sensors have been proven to be
accurate and durable. They have
an excellent long-term stability,
which decreases maintenance. The
superior performance of Vaisala
CARBOCAP
®
sensors results largely
Features/Benefi ts
Compact, wall-mounted
transmitter for demand-
controlled ventilation
Incorporates Vaisala
CARBOCAP®, the silicon based
NDIR sensor with unique
internal referencing
Advanced, single-beam, dual
wavelength measurement with
no moving parts
Excellent long-term stability
Ideal for ventilation control in
all types of occupied spaces
from the stable reference provided by
the electrically tunable Fabry-Perot
Interferometer (FPI).
The tunable FPI  lter measures CO
2
absorption, and simultaneously a
reference wavelength. This internal
reference measurement compensates
effectively for any changes in the
optical path, such as light source
intensity changes and contamination.
In the HVAC market, this type of
reference measurement is a unique
feature to Vaisala CARBOCAP
®
products, distinguishing them
from competitors’ comparative
products that do not have a reference
measurement at all, or have an
indirect reference measurement,
which is based on an assumed back-
ground CO
2
levels. In buildings with
around-the-clock occupancy (e.g.
hospitals, work-places, residential
buildings, retirement homes), the
assumed background CO
2
level
reference is simply not applicable.
The true internal reference
measurement of Vaisala CARBOCAP
®
CO
2
transmitters provides years of
stable CO
2
measurements.
The GMW115 Transmitter is designed
especially for DCV (Demand Controlled
Ventilation) applications with two
optional CO
2
measurement ranges of
0…2000 ppm and 0…5000 ppm.
4-Carbon-Dioxide-Pages-100-119-Vaisala-Catalog-2011.indd 112 24.10.2011 9.21
113
66.3
60
60
Ø 4.2
66.7
85.3
83.4
85.2
R2.1
124
120.9
25.8
84
R3.5
Technical Data
Performance
CO
2
-measurement range 0 ... 2000 ppm
0.....5000 ppm
Accuracy (including repeatability, non-
linearity and calibration uncertainty)
±(2 % of range + 2 % of
reading)
Long-term stability ± 5 % of range/5 years
Response time T90 1 min
Temperature dependence, typical -0,35 % of reading / °C
Pressure dependence, typical +0,15 % of reading/hPa
Warm-up time 1 min, 10 min for full.
specifi cation
Product lifetime > 10 years
Operating Environment
Temperature -5 ... +45 °C (23 ... 113 °F)
Humidity 0 ... 85 %RH
Pressure 700 ... 1200 hPa
Electromagnectic compatibility
Complies with EMS standard EN61326-1, Generic Environment
Inputs and Outputs
Operating voltage 24 V (±20 %) AC/DC
Power consumption <2 W
Outputs 4 … 20 mA, 0 … 10 V,
RS-485, 2-wire, non-isolated
Housing
Material: ABS plastics
Colour: Cycolac 233599/NCS 0502-G50Y
Fire resistance: UL94 HB
Ingress protection: IP30
Dimensions
Dimensions in mm
Ref. B210568EN-D ©Vaisala 2009
This material is subject to copyright protection, with all
copyrights retained by Vaisala and its individual partners. All
rights reserved. Any logos and/or product names are trademarks
of Vaisala or its individual partners. The reproduction, transfer,
distribution or storage of information contained in this brochure
in any form without the prior written consent of Vaisala is strictly
prohibited. All specifi cations — technical included — are subject
to change without notice.
For more information, visit
www.vaisala.com or contact
us at sales@vaisala.com
4-Carbon-Dioxide-Pages-100-119-Vaisala-Catalog-2011.indd 113 24.10.2011 9.21
Page view 114
1 2 ... 110 111 112 113 114 115 116 117 118 119 120 ... 161 162

Comments to this Manuals

No comments